How Dissolved Oxygen Contribute to a Successful Biological Wastewater Treatment

Potable Water & Municipal WastewaterOxygen (Dissolved)

Challenge

Online monitoring of dissolved oxygen (DO) is crucial in the biological treatment process of municipal wastewater, es­pecially when it comes to managing nutrient removal specif­ically the removal of nitrogen through processes like nitri­fication and denitrification. Here’s how DO plays a key role:

Optimizing Nitrification: Nitrification is the biological oxidation of ammonium (NH4+) to nitrate (NO3–), a process that requires the presence of oxygen. This process is carried out by aerobic bacteria, such as Nitrosomonas and Nitrobac­ter, which thrive in environments with sufficient DO levels. For effective nitrification, DO levels typically need to be maintained between 2.0 to 3.0 mg/L. If DO levels drop below this range, the nitrifying bacteria become less efficient, leading to incomplete conversion of ammonium to nitrate, which can result in ammonia breakthrough in the effluent.

Facilitating Denitrification: Denitrification is the reduction of nitrate to nitrogen gas (N2) by facultative anaerobic bacteria. This process occurs in anoxic conditions, where oxygen is absent or very low, and bacteria consume nitrate instead of oxygen. For effective denitrification, DO levels must be kept very low (usually less than 0.5 mg/L). If DO levels are too high, denitrification efficiency is reduced, resulting in higher nitrate levels in the effluent that do not meet regulatory standards.

Energy Efficiency: Aeration is one of the most energy-intensive operations in wastewater treatment plants. By monitoring DO levels, operators can optimize aeration – providing just enough oxygen to support microbial activity.

Solution

Wastewater characteristics can change fast due to varying inflows, industrial discharges, or storm events. It is therefore very valuable to set up online DO monitoring, which provides real-time data and allows rapid aeration adjustments to overcome the above challenges. Currently, one can find two main types of online DO sensors allow to control the biological wastewater treatment in a optimal way:

Electrochemical Sensor: The amperometric sensor technology (Clark sensor type) is often used for online DO applications and offers a high measurement sensitivity. To achieve constantly good readings with this application a quarterly air verification and sensor cleaning is required. The membrane and electrolyte exchange intervals are usually longer and should be done yearly. The good news is that the replacement will completely reset the life of the Clark sensor. It is important to know, that if an amperometric sensor is taken from the power supply, the electrodes must be polarized for about one hour until a correct reading is set up.

Optical (Luminescent) Sensors: Optical sensors use a luminescent dye that emits light when exposed to a specific wavelength. The presence of oxygen reduces the luminescence, and in principle the sensor measures the degree of luminescence reduction (quenching) to determine the DO concentration. These types of sensors are more expensive than electrochemical sensors and the life of the sensor is limited as the luminescent dye degrades over time (most suppliers are able to replace the sensor cap with the luminescent dye). Many suppliers state a two year replacement rate of the cap, but keep in mind that the luminescent dye is degrading faster the higher the measured oxygen amount is!

Both sensor types (electrochemical and optical) require regular membrane cleaning to deliver accurate DO measurements.

AMI Transmitter with Oxysafe Sensor and Oxydip

To ensure the biological treatment efficiency, many wastewater treatment plants use Swan's Oxysafe sensor together with the Oxydip immersion assembly to measure dissolved oxygen during nitrification and denitrification.

What you'll receive

  • Continuous measurement of dissolved oxygen

    • 0 – 20.0 ppm O2 (15 °C) or 0 – 200 % saturation

  • Very stable zero point and slope calibration

    • Accurate, temperature and pressure compensated dissolved oxygen readings

  • Robust and chemical inert oxygen permeable fluoropolymer membranes

    • The membrane is perfectly sealed to the front of the probe

    • This keeps the electrolyte free from poisoning

    • The membrane is never pulled over sharp edges, deformed or otherwise mechanically weakened

    • All these constructive characteristics add to the reliability and the longevity of the probeg

  • Easy maintenance and cleaning routines

    • Simply wipe the sensor head with a cloth or rinse the dirt away

    • Membrane exchange within 60 seconds

  • Very durable, safe and corrosion proof polyacetal-copolymer sensor housing

    • IP68 proofed

    • Easy and robust diaphragm concept

  • Cost sensitive and multifunctional immersion assembly

    • 45° immersion angle to avoid bubble creation on sensor head