Cation Conductivity (CC)Acid Conductivity (AC)pH (pH)

A-13.541.100
Transmitter AMI-II Deltacon Power AC
Dual-channel transmitter for specific (total) conductivity and cation (acid) conductivity.
Product Highlights
Selectable temperature compensation for varying sample qualities and alkalizing agents.
Calculation of pH value and alkalizing reagent concentration based on differential conductivity.
Details
The AMI-II Deltacon Power is a dual-channel transmitter for continuous monitoring of specific conductivity (SC) and cation conductivity (CACE). It calculates sample pH and alkalizing reagent concentration using differential conductivity. Designed for power and industrial plant applications, it is specialized for use with cation resin columns and provides accurate, real-time data to maintain optimal water chemistry and protect critical system components, with integrated flowmeter input.
| Conductivity measurement | for two 2-electrode conductivity sensor including integrated Pt1000 temperature sensor, e.g. SS UP-CON1000 |
| Measuring range | 0.055 - 1000 µS/cm |
| Accuracy (at 25 °C) | ±1% of measured value or ±1 digit (whichever is greater) |
| Temperature measurement (Pt1000) | |
|---|---|
| Measuring range | -30 to 250°C |
| Resolution | 0.1° C |
| Sample flow measurement | with digital sample flow meter. |
| Power Supply | |
| Voltage | 100-240 VAC (±10%), 50/60Hz / or 10-36 VDC |